14EN -
heating curve set 3
Index - String
MIN
value
MAX
value
Parameter function
25°C 65°C
This parameter indicates the minimum value of the heating set temperature, correspon-
ding with the maximum outside air temperature (index (C) user menu). This parameter is
only visible if the compensation function has been activated (index (5) user menu).
heating curve set 4
Index - String
MIN
value
MAX
value
Parameter function
-40°C 50°C
This parameter indicates the maximum outside air temperature taken into consideration
for heating compensation. This parameter is only visible if the compensation function has
been activated (index (5) user menu).
Setting domestic water temperature setpoint
Index - String
MIN
value
MAX
value
Parameter function
25°C 65°C
The heat pumps have a temperature limit setting for producing domestic water; this
setting indicates the processed water temperature above which the compressor stops.
Remember that to visualise this setting, parameter (A) of the installer menu must be
active (set value = 1) display.
Setting domestic water hysterisis
Index - String
MIN
value
MAX
value
Parameter function
1°C 20°C
This parameter indicates the proportional histerisis applied to the hot domestic water
set temp; this band produces the optimised management of the compressor, only
switching it on if the inlet/outlet water temperature (depending on the type of control set
by parameter (0) in the installer menu) is less than the hot domestic water set (parame-
ter (E) user menu), minus the value of this parameter.